Utilizing two-stage cascade compression technology and multi-stage refrigerant heat exchange, this system reduces the compression ratio during operation, significantly enhancing both efficiency and performance in low-temperature environments. It achieves an innovative water outlet temperature of 120°C even when the ambient temperature is as low as -35°C, serving as an effective replacement for heating boilers in extremely cold regions.
Features
1. Capable of delivering water outlet temperatures between 90°C and 120°C in ambient temperatures as low as -35°C.
2. Both stages incorporate industry-leading ultra-low-temperature DC inverters and enhanced vapor injection (EVI) technology.
3. Built-in Wi-Fi connectivity allows for remote monitoring, enabling you to check the heat pump’s operating status at a glance from anywhere.
Advantages
1. Exceptional Performance Across Various Conditions
The heat pump system provides efficient home heating, cooling, and domestic hot water, even in extreme cold. It is well-suited for use throughout most of Europe.
2. High-Quality Compressors
Equipped with Panasonic compressors, the system ensures reliable operation, creating an ideal, comfortable home environment.
3. EVI (Enhanced Vapor Injection) Technology
Thanks to EVI technology, the system maintains outstanding heating performance in low-temperature environments. It can supply 95°C hot water even when the outdoor temperature drops to -15°C, and it remains stable in extreme cold—down to -30°C.
4. Comprehensive Anti-Freeze Protection
The system employs multiple anti-freeze measures—including water pump circulation, system circulation, and base-pan heating—to automatically monitor the temperatures of the main unit and piping. If the ambient temperature falls below 2°C and the water temperature drops below 7°C, the heat pump automatically initiates heating to 15°C, effectively preventing the system from freezing.
5. Intelligent Defrosting
Using multiple sensors to monitor operating temperatures in real-time, the system performs intelligent defrosting based on actual requirements rather than a fixed schedule. This approach avoids unnecessary operation, resulting in greater efficiency and energy savings. Specifications
Type | FKH-20II/TGW | FKH-50II/TGW | FKH-100II/TGW | |
Top out wind | Top out wind | Top out wind | ||
Power specifications | 380V 3N~50Hz | 380V 3N~50Hz | 380V 3N~50Hz | |
Heating capacity under A1 operating | 20kW | 50kW | 100kW | |
Heating consumption power under A1 working | 12kW | 29kW | 58kW | |
Heating capacity under A2 working | 19kW | 49kW | 98kW | |
Heating consumption power under A2 | 12kW | 31kW | 62kW | |
Heating capacity under A3working condition( | 15kW | 42kW | 85kW | |
Heating consumption power under A3 | 11.5kW | 32kW | 63kW | |
Heating capacity under A4working condition(-20) | 14kW | 37kW | 75kW | |
Heating consumption power under A4 | 11.2kW | 30kW | 60kW | |
Maximum operating current | 36A | 70A | 140A | |
discharge | 3.4m³/h | 8.6m³/h≤ | 17.2m³/h | |
noise | ≤58dB(A) | 60dB(A) | ≤72dB(A) | |
Water side pressure loss | ≤75kPa | ≤75kPa | ≤88kPa | |
Unit size(length xwidth x height mm) | 860×780×1780 | 1550×780×1780 | 2260×1230×2170 | |
CONNECT SIZE | DN32(hexagon nipples) | DN40(hexagon nipples) | DN80(flange) | |
Unit weight(kg) | 240 | 450 | 1350 | |