Leomon
| Availability: | |
|---|---|
| Quantity: | |
Utilizing dual-stage compression technology and multi-stage refrigerant heat exchange, this system reduces the compression ratio during operation, significantly enhancing both the efficiency and the low-temperature performance of the heat pump. It achieves a breakthrough by delivering a water outlet temperature of 90°C even when the ambient temperature is as low as -35°C, serving as an ideal replacement for heating boilers in extremely cold regions.
Features
1. Capable of delivering water at 85–90°C, even in ambient temperatures as low as -35°C.
2. Both compression stages feature industry-leading ultra-low-temperature DC inverters and enhanced vapor injection (EVI) technology.
3. Built-in Wi-Fi connectivity allows for remote monitoring, enabling you to check the heat pump’s operating status from anywhere.
Advantages
1. Exceptional Performance Across All Conditions
The heat pump system provides efficient home heating, cooling, and domestic hot water, even in extreme cold. It is well-suited for use throughout most of Europe.
2. High-Quality Compressor
Equipped with a Panasonic compressor, the system ensures reliable operation, creating an ideal, comfortable home environment.
3. Enhanced Vapor Injection (EVI) Technology
EVI technology ensures superior heating performance in low-temperature environments. The system can deliver 90°C hot water even when the outdoor temperature is as low as -15°C, and it remains stable in extreme cold—down to -30°C.
4. Comprehensive Anti-Freeze Protection
The system employs multiple anti-freeze measures—including water pump circulation, system-wide circulation, and base-pan heating—to automatically monitor the temperatures of the main unit and piping. If the ambient temperature falls below 2°C and the water temperature drops below 7°C, the heat pump automatically initiates heating to 15°C, effectively preventing the system from freezing.
5. Intelligent Defrosting
Using multiple sensors to monitor operating temperatures in real-time, the system performs intelligent defrosting only when necessary. This approach is more efficient and energy-saving compared to traditional, timer-based defrosting methods. Specifications
Type | FKH-10I/CGW | FKH-18II/CGW | FKH-35II/CGW | FKH-70II/CGW | FKH-100II/CGW | FKH-130II/CGW |
Side air outlet | Top out wind | Top out wind | Top out wind | Top out wind | Top out wind | |
Power specifications | 220V~50Hz | 380V 3N~50Hz | 380V 3N~50Hz | 380V 3N~50Hz | 380V 3N~50Hz | 380V 3N~50Hz |
Heating capacity under A1 | 10kW | 18kW | 35kW | 70kW | 100kW | 130kW |
Heating consumption power under A1 | 4.8kW | 8.2kW | 16.8kW | 33.6kW | 47.6kW | 61.5kW |
Heating capacity under A2 working | 9.5kW | 17kW | 34kW | 68kW | 95kW | 125kW |
Heating consumption power under A2 | 5kW | 8.9kW | 17.9kW | 35.8kW | 50kW | 65.8kW |
Heating capacity under A3 working | 9.5kW | 17kW | 32kW | 64kW | 90kW | 110kW |
Heating consumption power | 6.2kW | 10.6kW | 20.6kW | 41.2kW | 56.5kW | 68.5kW |
Heating capacity under A4working | 8kW | 16kW | 30kW | 60kW | 80kW | 100kW |
Heating consumption power | 5.6kW | 11.1kW | 20.1kW | 40.2kW | 55.2kW | 68.9kW |
Maximum operating current | 40A | 35A | 70A | 120A | 160A | 200A |
discharge | 1.7m³/h | 3.1m³/h | 6m³/h | 12m³/h | 17.2m³/h | 24.1m³/h |
noise | ≤56dB(A) | ≤58dB(A) | ≤60dB(A) | ≤65dB(A) | ≤68dB(A) | ≤72dB(A) |
Water side pressure loss | ≤72kPa | ≤75kPa | ≤75kPa | ≤85kPa | ≤85kPa | ≤88kPa |
Unit size (length ×widthx height mm) | 1030×410×1390 | 860×780×1780 | 1550×780×1780 | 2260×1030×2170 | 2260×1230×2170 | 2260×1230×2170 |
CONNECT SIZE | DN32(hexagon | DN32(hexagon | DN40(hexagon | DN50(flange) | DN65(flange) | DN80(flange) |
Unit weight(kg) | 160 | 215 | 415 | 755 | 1110 | 1250 |
Please contact us for more information about our heat pumps. Our heat pump experts are ready to answer all your questions and provide a free quote.